P1.2 Application = Multipump(MultiDrive)
P3.15.3 Pump ID Number = 1
P3.15.4 Start & Feedback = Signals Connected
NOT USED (0...10V)
OUTPUT FREQUENCY
(0...20mA)
PID FEEDBACK (4...20mA)
24V auxilary voltage out
I/O ground
I/O ground
FAULT RESET
EXTERNAL FAULT
START FORWARD
Common for DI1-DI6
Common for DI1-DI6
24V auxilary voltage out
PUMP INTERLOCK
(Not in use by default)
Drive-To-Drive
Communication
(Modbus RTU)
Relay Output 1
(RUN)
Relay Output 2
(FAULT)
Relay Output 3
(READY)
FLUSHING
(Start Forward + Flushing Freq.)
PID SETPOINT SELECT.
(Open=Keypad SP1, Closed=Keypad SP2)
RO1
RO1
RO1
RO2
RO2
RO2
RO3
RO3
+10V
Illustration 22: Electric Wiring Diagram of the Multi-pump (Multidrive) System, Example 1C
1 sensor is connected to all the drives. The redundancy level of the system is low because only the drives are redundant.
If there is a drive failure, the next drive starts to operate as master.
If there is a sensor failure, the system stops.
AB298035655957en-000201 / DPD01083 | 51Danfoss A/S © 2023.08
Applications
VACON® 100 FLOW
Application Guide