Table 9: M1 Quick Setup
Index
Parameter
Min
Max
Unit
Default
ID
Description
1.2
Application
0
4
2
212
0 = Standard
1 = HVAC
2 = PID Control
3 = Multi-pump (single drive)
4 = Multi-pump (multidrive)
1.3
Minimum Frequency
Reference
0.00
P1.4
Hz
0.0
101
1.4
Maximum Frequency
Reference
P1.3
320.0
Hz
50.0/60.0
102
1.5
Acceleration Time 1
0.1
3000.0
s
5.0
103
1.6
Deceleration Time 1
0.1
3000.0
s
5.0
104
1.7
Motor Current Limit
IH*0.1
I
S
A
Varies
107
1.8
Motor Type
0
2
0
650
0 = Induction Motor
1 = Permanent Magnet Motor
2 = Reluctance Motor
1.9
Motor Nominal Volt-
age
Varies
Varies
V
Varies
110
Find this value U
n
on the nameplate of the mo-
tor.
NOTE! Find out if the motor connection is Delta
or Star.
1.10
Motor Nominal Fre-
quency
8.0
320.0
Hz
50/60
111
Find this value f
n
on the nameplate of the mo-
tor.
1.11
Motor Nominal Speed
24
19200
RPM
Varies
112
Find this value n
n
on the nameplate of the mo-
tor.
1.12
Motor Nominal Cur-
rent
IH * 0.1
I
S
A
Varies
113
Find this value I
n
on the nameplate of the mo-
tor.
1.13
Motor Cos Phi (Power
Factor)
0.30
1.00
Varies
120
Find this value on the nameplate of the motor.
1.14
Energy Optimization
0
1
0
666
0 = Disabled
1 = Enabled
1.15
Identification
0
2
0
631
0 = No action
1 = At standstill
2 = With rotation
1.16
Start Function
0
1
0
505
0 = Ramping
1 = Flying Start
1.17
Stop Function
0
1
0
506
0 = Coasting
1 = Ramping
1.18
Automatic Reset
0
1
0
731
0 = Disabled
1 = Enabled
AB298035655957en-000201 / DPD0108364 | Danfoss A/S © 2023.08
Applications
VACON® 100 FLOW
Application Guide