Parameter
Min
Max
Unit
Default
ID
Description
1.19
Response to External
Fault
0
3
2
701
0 = No action
1 = Alarm
2 = Fault (Stop according to stop mode)
3 = Fault (Stop by coasting)
1.20
Response to AI Low
Fault
0
5
0
700
0 = No action
1 = Alarm
2 = Alarm+preset fault frequency (P3.9.1.13)
3 = Alarm + previous frequency
4 = Fault (Stop according to stop mode)
5 = Fault (Stop by coasting)
1.21
Remote Control Place
0
1
0
172
0 = I/O control
1 = Fieldbus control
1.22
I/O Control Reference
A Selection
1
20
6
117
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID reference
8 = Motor potentiometer
11 = Block Out.1
12 = Block Out.2
13 = Block Out.3
14 = Block Out.4
15 = Block Out.5
16 = Block Out.6
17 = Block Out.7
18 = Block Out.8
19 = Block Out.9
20 = Block Out.10
1.23
Keypad Control Refer-
ence Selection
1
20
1
121
See P1.22.
1.24
Fieldbus Control Ref-
erence Selection
1
20
2
122
See P1.22.
1.25
AI1 Signal Range
0
1
0
379
0= 0...10 V/0...20 mA
1= 2...10 V/4...20 mA
1.26
AI2 Signal Range
0
1
1
390
0= 0...10 V/0...20 mA
1= 2...10 V/4...20 mA
1.27
RO1 Function
0
74
2
11001
See P3.5.3.2.1.
1.28
RO2 Function
0
74
3
11004
See P3.5.3.2.1.
1.29
RO3 Function
0
74
1
11007
See P3.5.3.2.1.
1.30
AO1 Function
0
31
2
10050
See P3.5.4.1.1.