Table 10: M1.34 Multi-pump (Multidrive)
Index
Parameter
Min
Max
Unit
Default
ID
Description
1.35.1
PID Gain
0.00
100.00
%
100.00
118
1.35.2
PID Integration Time
0.00
600.00
s
1.00
119
1.35.3
PID Derivation Time
0.00
100.00
s
0.00
132
1.35.4
Process Unit Selection
1
44
1
1036
See P3.13.1.4
1.35.5
Process Unit Min
Varies
Varies
Varies
1033
1.35.6
Process Unit Max
Varies
Varies
Varies
1034
1.35.7
Feedback 1 Source Selection
0
30
2
334
See P3.13.3.3
1.35.8
Setpoint 1 Source Selection
0
32
1
332
See P3.13.2.6
1.35.9
Keypad Setpoint 1
Varies
Varies
Varies
0
167
1.35.10
SP1 Sleep Frequency Limit
0.0
320.0
Hz
0.0
1016
1.35.11
SP1 Sleep Delay
0
3000
s
0
1017
0 = Not used
1.35.12
SP1 Wake Up Level
Varies
Varies
Varies
Varies
1018
0 = Not used
1.35.13
Multi-pump Mode
0
2
0
1785
0= Single drive
1= Multifollower
2= Multimaster
1.35.14
Number of Pumps
1
8
1
1001
1.35.15
Pump ID Number
1
8
1
1500
1.35.16
Start and Feedback Signals
0
2
1
1782
0 = Not connected
1 = Only Start Signal Con-
nected
2 = Both Signals Connec-
ted
1.35.17
Pump Interlocking
0
1
1
1032
0 = Disabled
1 = Enabled
1.35.18
Autochange
0
2
1
1027
0 = Disabled
1 = Enabled (interval)
2 = Enabled (weekdays)
1.35.19
Autochanged Pump
0
1
1
1028
0 = Auxiliary Pump
1 = All Pumps
1.35.20
Autochange Interval
0.0
3000.0
h
48.0
1029
1.35.21
Autochange Days
0
127
1786
1.35.22
Autochange Time of Day
Time
1787
1.35.23
Autochange: Frequency Limit
0.00
P3.3.1.2
Hz
25:00
1031
1.35.24
Autochange: Pump Limit
1
6
1030