5.7.6.4 AC Customer Socket
Table 36: Auxiliary Function Option Codes
Character po-
sition
Option
code
Description
23–24 A1 AC socket + cabinet light
AA AC socket + cabinet light + extended I/O terminals
AB AC socket + cabinet light + cabinet heater
AC AC socket + cabinet light + motor heater control
AD AC socket + cabinet light + insulation monitor
AE AC socket + cabinet light + extended I/O terminals + cabinet heater
AF AC socket + cabinet light + extended I/O terminals + motor heater control
AG AC socket + cabinet light + extended I/O terminals + insulation monitor
AH AC socket + cabinet light + extended I/O terminals + cabinet heater + motor heater control
AI AC socket + cabinet light + extended I/O terminals + cabinet heater + insulation monitor
AJ AC socket + cabinet light + extended I/O terminals + motor heater control + insulation monitor
AK AC socket + cabinet light + extended I/O terminals + cabinet heater + motor heater control + insu-
lation monitor
AL AC socket + cabinet light + cabinet heater + motor heater control
AM AC socket + cabinet light + cabinet heater + insulation monitor
AN AC socket + cabinet light + cabinet heater + motor heater control + insulation monitor
AO AC socket + cabinet light + motor heater control + insulation monitor
The socket provides a supply for measurement tools, equipment, or a computer. The socket type is CEE 7/3 ("Schuko", Type F) or NEMA
5-15 grounded (Type B). The default voltage is 230 V AC (IEC variant) and 115 V AC (UL variant). When using an external supply, the
maximum output power is 450 VA (IEC variant) and 230 VA (UL variant). When using a transformer supply, the maximum output power
is 200 VA for both variants.
Illustration 45: AC Customer Socket Terminals
Electrical Installation
Operating Guide | VLT® AQUA Drive FC 202