What to do if Danfoss Media Converter shows DC under voltage warning?
- AAaron BruceAug 26, 2025
If you're seeing a DC under voltage warning/alarm on your Danfoss Media Converter, it means the DC-link voltage has dropped below the undervoltage limit. The converter will then check for a connected 24 V DC back-up supply. If none is found, it will trip after a delay. To resolve this: * Check that the supply voltage matches the frequency converter voltage. * Perform an input voltage test. * Perform a soft charge circuit test.