Chapter 3 Electrical Wiring|VP3000
95
Sink Mode:
ON: activation voltage ≤ 9 V
DC
OFF: cut-off voltage ≥ 19 V
DC
Digital frequency signal
common
Digital frequency signal common
Multi-function Output 1–2
(photo coupler)
MO2 supports single-pulse output (basic output frequency
599 Hz)
As pulse output: max. current 48 V
DC
/ 50 mA
Not as pulse output: max. current 48 V
DC
/ 25 mA
Multi-function Output
Common (photo coupler)
Multi-function Output Common
Multi-function relay output 1
(N.O.) a
To output various kinds of monitoring signals such as motor
drive in operation, frequency reached, and overload
indication.
Resistive Load
3 A (N.O.) / 3 A (N.C.) 250 V
AC
3 A (N.O.) / 3 A (N.C.) 30 V
DC
Inductive Load (COS 0.4)
1.2 A (N.O.) / 1.2 A (N.C.) 250 V
AC
1.2 A (N.O.) / 1.2 A (N.C.) 30 V
DC
Multi-function relay output 1
(N.C.) b
Multi-function relay common
(Relay)
Multi-function relay output 2
(N.O.) a
Multi-function relay common
(Relay)
Potentiometer power supply
Power supply for analog frequency setting: +10–11 V
DC
/ 20
mA
Analog voltage frequency
command
⚫ The three analog input formats all support 0–10 V (AI3
default) and 0–20 mA / 4–20 mA (AI1 / AI2 default)
⚫ Voltage type input resistance: 164 kΩ;
Current type input resistance: 250 Ω
âš« The three analog input formats all support KTY84-130,
PTC, PT100 and PT1000. It is recommended to use
current signal input. Temperature range -20–200°C
Multi-function analog voltage
output
⚫ The two analog inputs both support 0–+10V / 0–20 mA /
4–20 mA
⚫ Under voltage mode (0–10 V), the max. output current is 2
mA
⚫ Voltage type load limit: > 5 kΩ;
Current type load limit: < 500 Ω
Analog signal common terminal
24V auxiliary power input
When the drive uses AC power input to the RST terminal, all
functions of the drive work normally. When the above power
supply at the input side of the drive is forced to be cut off due
to the supply end, the drive is powered off and shut down.
Some functions can continue operate through the 24V
auxiliary power input, as follows:
1. All communication cards work normally
2. Parameters and be read, written, and copied through
keypad, RS-485, USB and communication cards.
3. Keypad is able to display and operate normally