Chapter 10 Accessories | VP3000
666
Recommended maximum wiring gauge when installing zero-phase reactor
Model
Recommended wiring gauge
RF008X00A or RF008X00N
≤ 8 AWG
≤ 8.37 mm
2
RF004X00A or RF004X00N
≤ 4 AWG
≤ 21.15 mm
2
RF002X00A or RF410X00N
≤ 2 AWG
≤ 33.62 mm
2
Table 10-48
10-3-2-3 Zero-phase Reactor for Signal Cable
To solve interference problems between signal cables and electric devices, install a zero-
phase reactor on the signal cable. Install it on the signal cable which is the source of the
interference to suppress the noise for a better signal. The model names and dimensions are
listed in the table below.
Figure 10-47
Unit: mm
Model
A
B
C
Purpose
RF026X00N
10.7
17.8
8.0
To use with signal cable
RF020X00N
17.5
27.3
12.3
To use with signal cable
Table 10-49