Chapter 6 Drive Communication Network|VP3000
264
6-2-4 VP3000 BACnet Object and Property:
In VP3000, BACnet supports 3 types of object: Device, Analog Value (AV) and Binary Value (BV). In
each object type, we have the following table to show the Properties list:
Property ID
Object Type
Device
Analog Value
Binary Value
#4
ACTIVE_TEXT
V
#11
APDU_TIMEOUT
V
#12
APPLICATION_SOFTWARE_VERSION
V
#28
DESCRIPTION
V
V
V
#30
DEVICE_ADDRESS_BINDING
V
V
#36
EVENT_STATE
V
V
#44
FIRMWARE_REVISION
V
#46
INACTIVE_TEXT
V
#62
MAX_APDU_LENGTH_ACCEPTED
V
#63
MAX_INFO_FRAMES
V
#64
MAX_MASTER
V
#70
MODEL_NAME
V
#73
NUMBER_OF_APDU_RETRIES
V
#75
OBJECT_IDENTIFIER
V*
1
V
V
#76
OBJECT_LIST
V
#77
OBJECT_NAME
V*
1
V
V
#79
OBJECT_TYPE
V
V
V
#81
OUT_OF_SERVICE
V
V
#85
PRESENT_VALUE
V*
2
V*
2
#87
PRIORITY_ARRAY
V*
3
V*
3
#96
PROTOCOL_OBJECT_TYPES_SUPPORTED
V
#97
PROTOCOL_SERVICES_SUPPORTED
V
#98
PROTOCOL_VERSION
V
#104
RELINQUISH_DEFAULT
V*
3
V*
3
#107
SEGMENTATION_SUPPORTED
V
#111
STATUS_FLAGS
V
V
#112
SYSTEM_STATUS
V
#117
UNITS
V
#120
VENDOR_IDENTIFIER
V
#121
VENDOR_NAME
V
#139
PROTOCOL_REVISION
V
#155
DATABASE_REVISION
V
NOTE:
*1. The Object_ID and Object_Name Properties of Device are writeable.
*2. The Present_Value Property of some AV and BV objects is commandable.
*3. Only Commandable objects support Priority_Array and Relinquish_Default.