Chapter 10 Accessories | VP3000 
659 
 
10-3 Other Optional Accessories 
10-3-1 AC Reactors 
AC Input Reactor 
Installing an AC reactor on the input side of an AC motor drive can increase line impedance, improve 
the power factor, reduce input current, increase system capacity, and reduce interference generated 
from the motor drive. It also reduces momentary voltage surges or abnormal current spikes from the 
mains power, further protecting the drive. For example, when the main power capacity is higher than 
500 kVA, or when using a phase-compensation capacitor, momentary voltage and current spikes may 
damage the AC motor drive’s internal circuit. An AC reactor on the input side of the AC motor drive 
protects it by suppressing surges. 
 
NOTE: 
1.  When the power voltage exceeds the drive specification 380–480 V
AC
 with lower limit of ±20V, 
which is lower than 360 V
AC
 or higher than 500 V
AC
, it is not recommended to install an AC 
reactor. If you need to install an AC reactor under this input voltage level, ensure that the output 
equivalent inductance of the transformer in the factory is less than the following recommended 
value: 
 
 
     
  
For example: 
 
 , then it is not recommended to install an AC input reactor. 
2.  If a three-phase generator is used to supply power to the drive, the generator output voltage 
should be set within the input voltage specification range marked on the drive, that is 380 V
AC
 ≤ 
V
in
 ≤ 480 V
AC
. 
 
Installation 
Install an AC input reactor in series between the main power and the three input phases R S T, as 
shown in the figure below:   
 
Figure 10-41