Chapter 5 Initial Operation and Adjustment | VP3000 
222 
 
5-4-1-3 Adjustment Steps 
1.  Choose the motor control method. 
Set Pr. C0-02 = 0: VF. 
2.  Set IM1 VF curve selection. 
0: Manual VF curve 
1: 1.5th power V/F curve 
2: 2nd power V/F curve 
3: 60Hz with rated 50Hz 
4: 72Hz with rated 60Hz 
5: 50 Hz, 3rd power decreasing 
6: 50 Hz, 2nd power decreasing 
7: 60 Hz, 3rd power decreasing 
8: 60 Hz, 2nd power decreasing 
9: 50 Hz, Mid starting torque 
10: 50 Hz, Large starting torque 
11: 60 Hz, Mid starting torque 
12: 60 Hz, Large starting torque 
13: 90 Hz with rated 60 Hz 
14: 120Hz with rated 60 Hz 
15: 180Hz with rated 60 Hz 
5.  Execute no-load operation. 
If the motor operating direction is different from the definition, adjust Pr. A1-28 Forward Phase 
Selection = 1: UWV. 
6.  Check if the motor can operate to the operation frequency without abnormal sound. 
(1)  If the motor resonates, increase setting for Pr. E0-21 IM1 VF Hunt Compensation Gain. 
(2)  If there is motor excitation noise, increase setting for Pr. A5-00 Carrier Frequency 
Setting.