Chapter 3 Electrical WiringVP3000
100
Item
Definition
Standard
Performance
MTTF
d
Mean time to dangerous failure
Probability of Dangerous Failure on Demand
ISO13849-1
High
DC
Diagnostic Coverage
ISO13849-1
Medium
PTI
Proof Test Interval
IEC61508
20 years
Table 3-28
3-5-3 Terminal Function
Refer to Section 3-4 Control Circuit for description of STO function
The table below is the operation principle and display description after STO1 / STO2 signal input:
Signal
Status
STO1–SCM
ON
ON
OFF
OFF
STO2–SCM
ON
OFF
ON
OFF
Drive Output Status
Ready to output
STO2 mode
Torque output off
STO1 mode
Torque output off
STO mode
Torque output off
Fault Displays
No fault displays
STO2
STO1
STO
Response Time
N.A
≤ 6 ms
RESET
N.A
Directly reset
Directly reset
Directly reset
Table 3-29
STO means that Channel 1 and Channel 2 enable Safe Torque Off at the same time.
STO1 indicates that the difference between Channel 1 and Channel 2 is too large, and Channel 1
is active. Check the external wiring.
STO2 indicates that the difference between Channel 1 and Channel 2 is too large, and Channel 2
is active. Check the external wiring.
STL1 indicates Channel 1 internal circuit detected abnormal.
STL2 indicates Channel 2 internal circuit detected abnormal.
STO1–SCM / STO2–SCM ON: means STO1–SCM / STO2–SCM input voltage > 15 V
DC
power
STO1–SCM / STO2–SCM OFF: means STO1–SCM / STO2–SCM input voltage < 15 V
DC
power