Chapter 5 Initial Operation and Adjustment | VP3000
215
5-3-1-2 Adjustment Steps
1. Parameter Reset
Pr. b0-01 = 9: Reset 50 Hz default or 10: Reset 60 Hz default.
2. Set the operation command source.
Pr.
Parameter Name
Settings
A1-01
EX1 OPER Cmd Src
0: Disable
1: S1 Start
2: S1 Start, S2 Dir
3: S1 FWD, S2 REV
4: S1 Start, S2 Stop
5: S1 Start, S2 Stop, S3 Dir
6: S1 FWD, S2 REV, S3 Stop
7: Keypad
8: RS-485
9: USB
10: EX. COM
3. Set the frequency command source.
Pr.
Parameter Name
Settings
C1-01
EX1 Main FREQ Src
0: Disable
1: Keypad
2: RS-485
3: USB
4: EX. COM
7–9: AI1AI3
12–13: AI10–AI11
16: Up/down keys
17: Pulse Train
18: PID
4. Select motor autotune.
Refer to Section 5-3-2 IM Autotune or Section 5-3-3 SM Autotune.