Chapter 8 Troubleshooting|VP3000 
398 
 
8-1-3 PLC Fault Codes 
The device number in the 
downloaded program has 
exceeded the defined range 
Check if the device number used by the 
program has exceeded the model definition 1 
and re-download the program    
Device number write error during 
program execution 
Check the PLC program with D1014 and re-
download the program 
The read/ write device number or 
the uploaded command error 
during Modbus communication 
Check if the used communication address is 
correct and retransmit the communication 
packet 
Command error while downloading 
program 
Check whether the used API model supports 
the command and re-download the program   
Program exceeds memory capacity 
during program execution   
Check if the PLC program is correct and re-
download the program   
Command error during program 
execution 
Check the PLC program with D1014 and re-
download the program 
1.  If the FOR/NEXT command is written 
correctly 
2.  Is MC/ MCR paired 
3.  If the break command is written correctly 
4.  If the FOR/NEXT command is written 
correctly 
5.  If the break command is written correctly 
6.  Ensure the used model supports all API 
codes 
Checksum error during program 
execution 
Clear the current PLC program and re-
download the program 
Program has no END stop 
command 
Check if the PLC program is correct and re-
download the program 
Communication loss or the drive 
power off while downloading the 
program 
Check if the connection and the power supply 
is normal and re-download the program 
PLC scan time-out during program 
execution 
Check if the PLC program uses excessive 
FOR and CALL commands, reduce the 
usage and re-download the program.