Chapter 6 Drive Communication NetworkVP3000
248
6-1-3 Related Parameters
Modbus
NOTE: means that you can set this parameter during operation.
Pr.
Comm.
Address
Parameter Name
Description
Default
n0-00
0x1540
RS-485 COM Port Protocol
Sel
Defines RS-485 communication port
protocol selection
0: Modbus Slave
1: Modbus Master
2: BACnet MS/TP
0
n1-01
0x1581
Modbus Address
Defines the Modbus communication
address
1–254
1
n1-02
0x1582
Modbus COM Baud Rate
Defines the Modbus transmission speed
(Baud Rate).
0: 4.8 Kbps
1: 9.6 Kbps
2: 19.2 Kbps
3: 38.4 Kbps
4: 57.6 Kbps
5: 76.8 Kbps
6: 115.2 Kbps
1
n1-03
0x1583
Modbus Package Format
Defines the Modbus communication format
0: 7, N, 2 (ASCII)
1: 7, E, 1 (ASCII)
2: 7, O, 1 (ASCII)
3: 7, E, 2 (ASCII)
4: 7, O, 2 (ASCII)
5: 8, N, 1 (ASCII)
6: 8, N, 2 (ASCII)
7: 8, E, 1 (ASCII)
8: 8, O, 1 (ASCII)
9: 8, E, 2 (ASCII)
10: 8, O, 2 (ASCII)
11: 8, N, 1 (RTU)
12: 8, N, 2 (RTU)
13: 8, E, 1 (RTU)
14: 8, O, 1 (RTU)
15: 8, E, 2 (RTU)
16: 8, O, 2 (RTU)
0