Chapter 6 Drive Communication Network|VP3000 
249 
 
Modbus Timeout Check Time 
Defines communication timeout when the 
drive does not receive any signal in the 
setting time. Set the timeout check time as 
0 sec. to disable the timeout detection. 
0.0–100.0 sec. 
Defines the drive treatment after 
communication timeout when the control 
command source or the frequency 
command source is Modbus. 
0: Continue OPER 
1: Warning & continue OPER 
2: Fault & ramp to stop 
3: Fault & coast to stop 
Modbus Response Delay 
Time 
Defines the delay time of the drive 
responding to the upper Modbus package. 
0.0–200.0 ms 
0: Disable 
1: Enable 
bit0–1: Relay1–2 
bit2–3: MO1–MO2 
bit4–8: Reserve 
bit9–14: MO10–MO15 
0: Disable 
1: Enable 
bit0–1: AO1–2 
bit2–3: Reserve 
bit4–5: AO10–AO11 
Modbus Master Target 
Selection 
0: None 
1: InnerPLC 
2: D2D 
Code Description 
The communication protocol is in hexadecimal, ASCII: ”0”…“9”, “A”…“F”, every hexadecimal value 
represents an ASCII code. For example: