Chapter 6 Drive Communication NetworkVP3000
249
Pr.
Comm.
Address
Parameter Name
Description
Default
n1-04
0x1584
Modbus Timeout Check Time
Defines communication timeout when the
drive does not receive any signal in the
setting time. Set the timeout check time as
0 sec. to disable the timeout detection.
0.0–100.0 sec.
0.0
n1-05
0x1585
Modbus Timeout Disposal
Defines the drive treatment after
communication timeout when the control
command source or the frequency
command source is Modbus.
0: Continue OPER
1: Warning & continue OPER
2: Fault & ramp to stop
3: Fault & coast to stop
0
n1-06
0x1586
Modbus Response Delay
Time
Defines the delay time of the drive
responding to the upper Modbus package.
0.0–200.0 ms
2.0
n1-07
0x1587
Modbus MO Mask
0: Disable
1: Enable
bit0–1: Relay1–2
bit2–3: MO1–MO2
bit4–8: Reserve
bit9–14: MO10–MO15
0
n1-08
0x1588
Modbus AO Mask
0: Disable
1: Enable
bit0–1: AO1–2
bit2–3: Reserve
bit4–5: AO10–AO11
0
n1-09
0x1589
Modbus Master Target
Selection
0: None
1: InnerPLC
2: D2D
0
Code Description
The communication protocol is in hexadecimal, ASCII: ”0”…“9”, “A”…“F”, every hexadecimal value
represents an ASCII code. For example:
Character
‘0’
‘1’
‘2’
‘3’
‘4’
‘5’
‘6’
‘7’
ASCII code
30H
31H
32H
33H
34H
35H
36H
37H
Character
‘8’
‘9’
‘A
‘B’
‘C’
‘D’
‘E’
‘F’
ASCII code
38H
39H
41H
42H
43H
44H
45H
46H