Chapter 3 Electrical WiringVP3000
102
Control loop wiring
1. Default wiring
The S24V-STO1-STO2 terminals are shorted together as default wiring. If you need to use the
Safety function (refer to wiring method 2 & 3), remove the short-circuit.
Figure 3-46
2. Built-in 24V power wiring
Remove the short-circuit of S24V-STO1-STO2.
As shown in the figure below, the ESTOP switch must be closed in normal situation so the
drive can output normally.
In STO mode, the ESTOP switch is turned ON, the drive stops output, and the keypad
displays STO.
With this connection, the SCM does not need to be wired (empty connection). Connect 24V
Safety dedicated power terminal, do NOT use the general +24V terminal power supply.
Figure 3-47