Chapter 5 Initial Operation and Adjustment | VP3000
243
9. Test loading capacity at high-frequency.
(1) If the loading capacity at high-frequency is insufficient or the response is slow, increase
setting for Pr. F1-09 Observer High Speed Gain.
(2) If the high-frequency current is unstable or the output frequency fluctuates too much,
decrease setting for Pr. F1-09 Observer High Speed Gain.
10. If the response is slow during acceleration and deceleration, increase setting for Pr. F1-10 PLL
P Gain or Pr. F1-11 PLL I Gain.