Chapter 7 Second Development PlatformVP3000
385
END
M13
M1044
FREQP
K300 K0 K0
FREQ
K3000 K50 K60
M11
M10
M10
M11
M1000
M1040
M12
M1042
M1000
M1025
M11
M1026
M14
M1052
Pr. L0-01 is defined as whether the reference command before PLC execution is cleared.
bit 0: before the PLC scan, whether the target frequency is cleared to be 0.
(PLC is ON, and FREQ instruction is in the program)
For example: when a user is writing a program,
END
K2000
M0
K1000
K1000
FREQ
we force M0 to be 1, then the frequency command is 20.00 Hz. If M0 = 0, it has different
situations:
Case1: when Pr.L0-01 bit0 is 0, and M0 = 0, then the frequency command remains at 20.00 Hz.
Case2: when Pr.L0-01 bit0 is 1, and M0 = 0, then the frequency command becomes 0.00 Hz.
This is because that before the PLC scans the programs, when Pr.L0-01 bit0 = 1, the frequency
will be cleared to be 0 first; when Pr.L0-01 bit0 = 0, the action to clear the frequency to be 0 is
not performed.