Chapter 8 Troubleshooting|VP3000 
410 
 
Warning Setting Parameter 
Pr. H5-00 (ot Action) = 0 
0: Warning & continue OPER 
1: Fault & Ramp to Stop 
2: Fault & Auto-Decel 
3: Fault & coast to stop 
4: Fault & by Quick Stop Time 
The ot1 warning automatically clears when the output current is < (Pr. H5-04 × 
95%) 
The ot1 warning automatically clears when the output current is < (Pr. H5-04 × 
95%) 
Incorrect parameter setting 
Reset Pr. H5-04 and Pr. H5-05. 
Mechanical failure 
(E.g., over-torque, mechanical 
lock)   
Rule out the causes of malfunction. 
Reduce the load. 
Replace the motor with a larger capacity model. 
Accel./Decel. time and working 
cycle are too short 
Increase the setting values for Pr. C2-00–Pr. C2-07 (accel./decel. time) 
Adjust  settings  for  Pr.E0-04,  E0-06,  E0-08,  E1-04,  E1-06,  E1-08  (V/F  curve). 
Adjust the setting value for the mid-point voltage (if the mid-point voltage is set 
too small, the load capacity decreases at low speed). 
The motor capacity is too small 
Replace the motor with a larger capacity model. 
Overload during low-speed 
operation 
Decrease low-speed operation time. 
Enlarge the motor capacity. 
Torque compensation is too large 
Adjust the torque compensation (refer to Pr. E0-16 torque compensation gain) 
until the current reduces and the motor does not stall. 
Improper parameter settings for 
speed tracking function 
(Including restart after momentary 
power loss and restart after fault)   
Correct the parameter settings for speed tracking. 
Start the speed tracking function. 
Adjust the maximum current for Pr. A3-01 speed tracking.