Chapter 8 Troubleshooting|VP3000 
420 
 
Over slip warning On the basis of the maximum slip (Pr. H5-50). When the 
motor drive outputs at constant speed, F > H or F < H exceeds the level set via 
Pr. H5-54, and it exceeds the time set via Pr. H5-55, oSL shows. oSL occurs in 
induction motors only. 
When the drive outputs at constant speed, and F > H or F < H exceeds the Pr. 
H5-54 level 
Warning Setting Parameter 
H5-48 
0: Warning & continue OPER 
1: Fault & Ramp to Stop 
2: Fault & Auto-Decel 
3: Fault & coast to stop 
4: Fault & by Quick Stop Time 
The oSL warning is automatically cleared when Pr. H5-48 = 0, the drive outputs 
at constant speed, and F > H or F < H does not exceed the Pr. H5-54 level 
anymore. 
Any of the motor parameters in 
parameter group 5 may be 
incorrect 
Check the motor parameter. 
Check if Pr. H5-54, Pr. H5-55, and 
Pr. H5-48 are properly set. 
Check the parameter settings for oSL protection.