Chapter 8 Troubleshooting|VP3000 
429 
 
PLC save memory error 
(PLSv)   
Device number write error during program execution 
The program detects incorrect written address (e.g., the address has exceeded 
the range) during PLC operation, then the PLSv warning shows. 
Immediately act when the error is detected 
Warning Setting Parameter 
Check if the program is correct and re-download the program. If the fault does 
not exist, the warning automatically clears. 
An incorrect written address is 
detected during PLC operation 
Check the PLC program with D1014 and re-download the program.