Chapter 8 Troubleshooting|VP3000 
492 
 
Over-current during 
deceleration   
(ocd)   
Output current exceeds 1.9 times of rated current during deceleration. When 
ocd occurs, the drive closes the gate of the output immediately, the motor runs 
freely, and the display shows an ocd error. 
190% of the rated current 
Fault Treatment Parameter 
Reset in 5 sec. after the fault is cleared 
Deceleration time is too short 
1.  Increase the deceleration time 
2.  Increase the deceleration time of S-curve (Pr. C2-08–C2-11) 
3.  Adjust the accel/decel time (Pr.C2-00–C2-07)   
4.  Set over-current stall prevention function (Pr. H2-05–H2-07)     
5.  Replace the drive with a larger capacity model 
Check if the mechanical brake of 
the motor activates too early 
Check the action timing of the mechanical brake. 
Short circuit at motor output due to 
poor insulation wiring 
Check the motor cable and remove causes of the short  circuits or replace the 
cable before turning on the power. 
Check for possible burnout or 
aging insulation of the motor 
Check the motor insulation value with megger. Replace the motor if the insulation 
is poor. 
Check if the output current during the whole working process exceeds the AC 
motor  drive’s  rated  current.  If  yes,  replace  the AC  motor  drive  with  a  larger 
capacity model. 
Impulsive change of the load 
Reduce the load or increase the capacity of AC motor drive. 
Use special motor or motor with 
larger capacity than the drive 
Check the motor capacity (the rated current on the motor’s nameplate should ≤ 
the rated current of the drive)   
Use ON/OFF controller of an 
electromagnetic contactor at the 
output (U/V/W) of the drive 
Check the action timing of the contactor and make sure it is not turned ON / 
OFF when the drive outputs the voltage. 
Adjust V/F curve setting and frequency/voltage. When the fault occurs, and the 
frequency voltage is too high, reduce the voltage. 
Torque compensation is too large 
Adjust the torque compensation (refer to Pr. E0-16 torque compensation gain) 
until the current reduces and the motor does not stall. 
Malfunction caused by 
interference 
Verify the wiring of the control circuit and wiring/grounding of the main circuit to 
prevent interference. 
The length of motor cable is too 
long 
Enlarge the AC motor drive’s capacity. 
Install AC reactor(s) on the output side (U/V/W).