Chapter 8 Troubleshooting|VP3000 
495 
 
When the AC motor drive detects that (one of) the output terminal(s) is 
grounded and the grounding current is higher than Pr. H2-00 setting value, GFF 
occurs. 
NOTE: the short circuit protection is provided for AC motor drive protection, not 
to protect the user. 
Pr. H2-00 (Default = 60%)   
Fault Treatment Parameter 
Reset in 5 sec. after the fault is cleared 
Motor burnout or aging insulation 
occurred 
Check the motor insulation value with megger. Replace the motor if the insulation 
is poor. 
Short circuit due to broken cable 
Troubleshoot the short circuit. 
Replace the cable. 
Larger stray capacitance of the 
cable and terminal 
If the motor cable length exceeds 100 m, decrease the setting value for carrier 
frequency. 
Take remedies to reduce stray capacitance. 
Malfunction caused by 
interference 
Verify the wiring and grounding of the communication circuit. It is recommended 
to separate the communication circuit from the main circuit, or wire in 90 degrees 
for effective anti-interference performance. 
Cycle the power after checking the status of motor, cable, and cable length. If 
GFF still exists, return to the factory for repair.