Chapter 8 TroubleshootingVP3000
501
ID No.
Fault Name
Descriptions
10
Over-voltage at stop
(ovS)
Over-voltage at stop
Action and Reset
Action Condition
460V models: 820 V
DC
Action Time
Immediately acts when DC bus voltage is higher than the condition
Fault Treatment Parameter
No
Reset Method
Manual reset
Reset Condition
Reset only when DC bus voltage is lower than 90% of the over-voltage condition
Record
Yes
Cause
Corrective Actions
Power voltage is too high
Check if the input voltage is within the rated AC motor drive input voltage range,
and check for possible voltage spikes.
ON/OFF switch action of phase-in
capacitor in the same power
system
If the phase-in capacitor or active power supply unit acts in the same power
system, the input voltage may surge abnormally in a brief time. In this case, install
an AC reactor.
Malfunction caused by
interference
Verify the wiring of the control circuit and wiring/grounding of the main circuit to
prevent interference.
Hardware failure in voltage
detection
Check if other error code such as cd1–cd3 occur after cycling the power. If yes,
return to the factory for repair.
Motor ground fault
The ground short circuit current charges the capacitor in the main circuit through
the power. Check if there is ground fault on the motor cable, wiring box and its
internal terminals.
Troubleshoot the ground fault.