Chapter 8 Troubleshooting|VP3000 
501 
 
Over-voltage at stop   
(ovS)   
Immediately acts when DC bus voltage is higher than the condition 
Fault Treatment Parameter 
Reset only when DC bus voltage is lower than 90% of the over-voltage condition 
Power voltage is too high 
Check if the input voltage is within the rated AC motor drive input voltage range, 
and check for possible voltage spikes. 
ON/OFF switch action of phase-in 
capacitor in the same power 
system 
If  the  phase-in  capacitor  or  active  power  supply  unit  acts  in  the  same  power 
system, the input voltage may surge abnormally in a brief time. In this case, install 
an AC reactor. 
Malfunction caused by 
interference 
Verify the wiring of the control circuit and wiring/grounding of the main circuit to 
prevent interference. 
Hardware failure in voltage 
detection   
Check if other error code such as cd1–cd3 occur after cycling the power. If yes, 
return to the factory for repair. 
The ground short circuit current charges the capacitor in the main circuit through 
the power. Check if there is ground fault on the motor cable, wiring box and its 
internal terminals. 
Troubleshoot the ground fault.