Chapter 8 Troubleshooting|VP3000 
507 
 
Capacitor overheating   
(oH2)   
The drive has detected the capacitors are overheat and the temperature exceeds 
Pr. H4-01 warning protection level 
When Pr.H4-01 is higher than the IGBT overheating protection level, oH2 error 
occurs instead of oH2 warning. 
Capacitor temperature exceeds the protection level for more than 1 second, oH2 
error occurs. 
Fault Treatment Parameter 
Resets when the capacitor temperature is lower than the oH2 warning   
Check if the ambient temperature 
or temperature inside the cabinet 
is too high, or if there is 
obstruction in the ventilation hole 
of the control cabinet. 
Check the ambient temperature. 
Regularly inspect the ventilation hole of the control cabinet. 
Change the installed place if there are heating objects, such as braking resistors, 
in the surroundings. 
Install  / add  cooling  fan or  air  conditioner to  lower  the temperature  inside the 
cabinet. 
Check if there is any obstruction 
on the heat sink or if the fan is 
running 
Remove the obstruction or replace the cooling fan. 
Insufficient ventilation space 
Increase ventilation space of the drive. 
Check if the drive matches the 
corresponded loading. 
1.  Reduce the load. 
2.  Decrease the carrier. 
3.  Replace the drive with a larger capacity model. 
The drive has run 100% or more 
of the rated output for a long time 
Replace the drive with a larger capacity model. 
The load changes frequently 
Reduce the changes of the load.