Chapter 8 Troubleshooting|VP3000 
510 
 
The AC motor drive detects excessive drive output current. The overload 
capacity sustains for 1 minute when the drive outputs 110% of the drive’s rated 
output current. 
Based on overload curve and derating curve   
When the load is higher than the protection level and exceeds allowable time, 
the oL protection activates 
Fault Treatment Parameter 
Reset in 5 sec. after the fault is cleared 
Accel./Decel. time and working 
cycle are too short 
Increase the setting values for Pr. C2-00–Pr. C2-07 (accel./decel. time) 
Adjust settings for Pr.E0-03–E0-14 (V/F curve). Adjust the setting value for the 
mid-point  voltage  (if  the  mid-point  voltage  is  set  too  small,  the  load  capacity 
decreases at low speed). 
Refer to the V/F curve selection of Pr. E0-00. 
The capacity of the drive is too 
small 
Replace the motor with a larger capacity model. 
Overload during low-speed 
operation 
Decrease low-speed operation time. 
Enlarge the AC motor drive’s capacity. 
Decrease the carrier frequency of Pr. A5-00. 
Torque compensation is too large 
Adjust the torque compensation (refer to Pr. E0-16 torque compensation gain) 
until the current reduces and the motor does not stall. 
Check if the setting for stall 
prevention is correct 
Set the stall prevention to the proper value. 
Check the status of three-phase motor. 
Check if the cable is broken or the screws are loose. 
Improper parameter settings for 
speed tracking function 
(Including restart after momentary 
power loss and restart after fault)   
Correct the parameter settings for speed tracking. 
Start the speed tracking function. 
Adjust the maximum current for Pr. A3-01 speed tracking.