Chapter 8 Troubleshooting|VP3000 
518 
 
Motor overheating   
(oH3) PT100 
Motor overheating (PT100) (Pr. H6-03 = 3 PT100), when PT100 temperature is 
> Pr. H6-07 setting value, the fault treatment acts according to Pr. H6-09. 
PT100 temperature > Pr.06-07 setting   
Fault Treatment Parameter 
Pr. H6-09 
0: Warning & continue OPER 
1: Fault & Ramp to Stop 
2: Fault & Auto-Decel 
3: Fault & coast to stop 
4: Fault & by Quick Stop Time 
When Pr. H6-09 = 0 and when the temperature is < Pr. H6-07 level, the oH3 is 
automatically cleared. 
It is “Fault” when Pr. H6-09 = 1–4, which must be reset manually. 
Records when Pr. H6-09 = 1–4 and oH3 displays “Fault” 
Clear the motor lock status. 
Reduce the load. 
Enlarge the motor capacity. 
Ambient temperature is too high 
Change the installed place if there are heating devices in the surroundings. 
Install / add cooling fan or air conditioner to lower the ambient temperature. 
Motor cooling system error 
Check the cooling system to make it work normally. 
Operates at low speed too long 
Decrease low-speed operation time. 
Change to dedicated motor for the drive. 
Enlarge the motor capacity. 
Accel./Decel. time and working 
cycle are too short 
Increase the setting values for Pr. C2-00–Pr. C2-07 (accel./decel. time) 
Adjust settings for Pr.E0-03–E0-14 (V/F curve). Adjust the setting value for the 
mid-point voltage (if the mid-point voltage is set too small, the load capacity 
decreases at low speed). 
Check if the motor rated current 
matches that on the motor 
nameplate 
Reset to the correct motor rated current. 
Check if the PT100 is properly set 
and wired 
Check  the  connection  between  PT100  thermistor  resistor  and  the  heat 
protection. 
Check if the setting for stall 
prevention is correct 
Set the stall prevention to the proper value.