Chapter 8 TroubleshootingVP3000
558
ID No.
Fault Name
Descriptions
96
Power board
communication error
(PMCF)
Power board communication error
Action and Reset
Action Condition
Internal communication time-out
Action Time
Immediately act
Fault Treatment Parameter
No
Reset Method
Auto-reset
Reset Condition
Communication recovers
Record
Yes
Cause
Corrective Actions
Malfunction caused by
interference
Verify the wiring of the control circuit and wiring/grounding of the main circuit to
prevent interference.
Hardware failure
Check if other error code occurs after cycling the power. If yes, return to the
factory for repair.