Chapter 8 Troubleshooting|VP3000
582
DC test error while motor parameter auto-tuning
Fault Treatment Parameter
Incorrect settings for the motor
parameter
Verify the settings of parameter group d are correct.
Motor wiring is incorrect
Check if the motor wiring is correct.
Check if the motor works normally.
The motor U/V/W wire is abnormal
Check if the wire is broken.
The electromagnetic contactor is
ON at output side (U/V/W) of the
drive
Make sure the electromagnetic valve is OFF.