Chapter 8 TroubleshootingVP3000
602
ID No.
Fault Name
Descriptions
306
ExCom card break
(ECCb)
Communication cards break off warning
Action and Reset
Action Condition
Communication cards break off
Action Time
The time between communication card break off and ECCb displays:
1. EtherNet/IP: 5 sec.
2. Modbus TCP: 5 sec.
3. DeviceNet: 1 sec.
4. PROFIBUS: 1 sec.
5. EtherCAT: 0.1 sec.
Warning Setting Parameter
N/A
Reset Method
Auto resets after communication card is re-installed
Reset Condition
Immediately reset
Record
No
Cause
Corrective Actions
Communication cards break off
Re-install communication card