Chapter 10 Accessories | VP3000 
648 
 
NS LED 
No power supply or CMC-DN01 
does not pass the MAC ID test 
1. Check the power of CMC-DN01 and see if the 
connection is normal. 
2. Make sure at least one or more nodes are on 
the bus. 
3. Check if the serial transmission speed of 
CMCDN01 is the same as that of other nodes. 
CMC-DN01 is on-line but does not 
connect to the master 
1.  Configure CMC-DN01 to the scan list of the 
master. 
2.  Re-download the configured data to the 
master. 
CMC-DN01 is on-line and 
normally connects to the master 
CMC-DN01 is on-line, but I/O 
connection is timed-out 
1.  Check if the network connection is normal. 
2.  Check if the master operates normally. 
The communication is down 
MAC ID test failure 
No network power supply 
CMC-DN01 is off-line 
1.  Make sure all the MAC IDs on the network are 
not repeated 
2.  Check if the network installation is normal 
3.  Check if the baud rate of CMC-DN01 is 
consistent with that of other nodes 
4.  Check if the node address of CMC-DN01 is 
illegal 
5.  Check if the network power supply is normal 
No power supply or being off-line 
Check the power supply of CMC-DN01 and see if 
the connection is normal 
Switch the master PLC to RUN status 
1.  Reconfigure CMC-DN01 
2.  Re-power AC motor drive 
1.  See the fault code displayed on the AC motor 
drive 
2.  Send back to the factory for repair if necessary 
CMC-DN01 is establishing 
connection with AC motor drive 
If the flashing lasts for a long time, turn off the 
power and check if CMC-DN01 and AC motor 
drive are correctly installed and normally 
connected to each other.