Chapter 3 Electrical WiringVP3000
74
Frame B2
Figure 3-14
If you install at Ta 50°C environment, use coper wires that have a voltage rating of 600V and are
temperature resistance to 75°C or 90°C.
If you install at Ta 50°C above environment, use copper wires that have a voltage rating of 600V
and are temperature resistance to 90°C or above.
For VFD018VP43BFTAA models: if you install at Ta 40°C above environment, use copper wires that
have a voltage rating of 600V and are temperature resistance to 90°C or above.
To be UL installation resistance of 75°C, in accordacne with UL requirements and
recommendations. Do not reduce the wire gauge when using high-temperature resistant wire.
Stripping length: 7–8 mm
Model
Main Circuit Terminals
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3
Terminal
Max. Wire
Gauge
Min. Wire
Gauge
Screw Spec.
and Torque
(±10%))
Max. Wire
Gauge
Min. Wire
Gauge
Screw Spec.
and Torque
(±10%))
VFD013VP43BFTAA
6 mm
2
(10 AWG)
6 mm
2
(10 AWG)
6 kg-cm
(5.2 lb-in.)
(0.59 Nm)
6 mm
2
(10 AWG)
6 mm
2
(10 AWG)
6 kg-cm
(5.2 lb-in.)
(0.59 Nm)
VFD018VP43BFTAA
6 mm
2
(10 AWG)
6 mm
2
(10 AWG)
Table 3-8