B-11
APPENDIX B/ Technical Specifications
Setup
parameters
(continued)
The following table lists the default settings for the threshold parameters in each
monitoring mode.
*Numbers are in percent of nominal unless otherwise specified.
Parameters
Standard
Power
Quality
Motor
Current
Inrush
Fault
Recorder
Long-term
Timed
Recording
Continuous
Data
Logging
EN50160 Motor
Quality
Energy
Audit
IEC / IEEE
Transients (continued)
Cycle-by-
cycle
Waveshape
Duration
(% of cycle)
10% Off 10% Off Off 10% 10% Off
Waveform
Duration
7% Off 7% Off Off 7% 7% Off
Waveform Capture Trigger Response
When
Volts go
out, record:
All
Active
Channels
Off All
Active
Vo l t
Channels
Off Off All
Active
Channels
All
Active
Channels
All
Active
Channels
When
Amps go
out, record:
Fault
Amps
Channels
Fault
Amps
Channels
Fault
Amps
Channels
Off Off Fault
Amps
Channels
Fault
Amps
Channels
Fault
Amps
Channels
Journal Intervals
Volts 10
minutes
Off Off 10
minutes
1 second 10
minutes
10
minutes
10
minutes
Amps 10
minutes
Off Off 10
minutes
1 second 10
minutes
10
minutes
10
minutes
Power 10
minutes
Off Off 10
minutes
1 second 10
minutes
10
minutes
10
minutes
Demand 15
minutes
Off Off 15
minutes
Off 15
minutes
15
minutes
5
minutes
Energy 10
minutes
Off Off 10
minutes
10
minutes
10
minutes
10
minutes
10
minutes
Harmonics 10
minutes
Off Off 10
minutes
Off 10
minutes
10
minutes
10
minutes
Flicker
(Pst)
10
minutes
Off Off 10
minutes
Off 10
minutes
10
minutes
Off
Flicker
(Plt)
2 hours Off Off 2 hours Off 2 hours 2 hours Off
Characterizer
Mode
IEC 4-30
/
IEEE 1159
None None IEEE 1159 None IEC
61000-4-30
IEEE
1159
None