B-13
APPENDIX B/ Technical Specifications
DRANFLEX
300MHB Series
probes
DRANFLEX 300MHB SERIES PROBE SPECIFICATIONS
Type: Flexible
Installation Category
: 1000 VRMS, CAT III, Pollution Degree 2
DRANFLEX
3000XLB/
6000XLB Series
probes
DRANFLEX 3000XLB/6000XLB SERIES PROBE SPECIFICATIONS
Type: Flexible
Installation Category
: 1000 VRMS, CAT III, Pollution Degree 2
Model Range Amplitude
Accuracy
±
Phase
Accuracy
+/-
Frequency
Range
Maximum
Conductor
Size
DRANFLEX
300MHB
6/8/12
0.3A to
300A
(3 ranges)
0.3A to 3A 1% rdg,
±0.1A
25Hz to
75KHz
50/70/100
mm dia.
0.3A to 3A 1% rdg,
±0.1A
30A to 3000A 1% rdg,
±0.5A
Model Range Amplitude
Accuracy
±
Phase
Accuracy
+/-
Frequency
Range
Maximum
Conductor
Size
DRANFLEX
3000XLB
DRANFLEX
3003XLB
24/36/48
3A to
3000A
(3 ranges)
3A to 30A 1% rdg,
±0.1A
10Hz to
10KHz
200/280/
430 mm
dia.
30A to 300A 1% rdg,
±0.1A
300A to
3000A
1% rdg,
±1A
DRANFLEX
6000XLB
DRANFLEX
6003XLB
24/36/48
6A to
6000A
(3 ranges)
6A to 60A 1% rdg,
±0.1A
10Hz to
10KHz
200/280/
430 mm
dia.
60A to 600A 1% rdg,
±0.1A
600A to
6000A
1% rdg,
±1A
Shop for Power Metering products online at:
1.877.766.5412
www.PowerMeterStore.com

Table of Contents

Other manuals for Dranetz hdpq xplorer

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dranetz hdpq xplorer and is the answer not in the manual?

Dranetz hdpq xplorer Specifications

General IconGeneral
BrandDranetz
Modelhdpq xplorer
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals