B-10
Parameter Settings in Each Monitoring Mode
Parameter Settings in Each Monitoring Mode
Setup
parameters
The following table lists the default settings for the threshold parameters in each
monitoring mode.
Continued on next page
Parameters
Standard
Power
Quality
Motor
Current
Inrush
Fault
Recorder
Long-term
Timed
Recording
Continuous
Data
Logging
EN50160 Motor
Quality
Energy
Audit
IEC / IEEE
RMS Variation
High Limit 110% 120% 110% Off Off 110% 110% 110%
Low Limit 90% Off 90% Off Off 90% 90% 90%
Ver y L o w
Limit
1% / 10%
Off 10% Off Off 1% 10% Off
RMS
Pre-trigger
(cycles)
644 0 1 66 1
RMS In-Out
Post-trigger
(cycles)
60 200 100 0 2 6 6 8
RMS Out-In
Post-trigger
(cycles)
60 200 1000 0 2 6 6 8
Waveform
Capture
Pre-trigger
(cycles)
244 0 1 22 1
Waveform
Capture
Post-trigger
(cycles)
2 200 1000 10 (50 Hz);
12 (60 Hz)
(snapshots)
2228
Transients
Absolute
Instantaneous
Peak
170% 350% 170% Off Off 170% 170% Off
High
Frequency
100% Off 100% Off Off 100% 100% Off
Cycle-by-
cycle
Waveshape
Magnitude
10% Off 10% Off Off 10% 10% Off
Shop for Power Metering products online at:
1.877.766.5412
www.PowerMeterStore.com

Table of Contents

Other manuals for Dranetz hdpq xplorer

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dranetz hdpq xplorer and is the answer not in the manual?

Dranetz hdpq xplorer Specifications

General IconGeneral
BrandDranetz
Modelhdpq xplorer
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals