4. Exit from the menu 1 Refrigeration point by tapping the ESC button once and select menu 6 Configuration
- 2 Controller.
6 Configuration - 2 Controller
REGLER POS: XXX
1 Type and version Type, serial number and Master / Slave (ON/OFF)
2 Temperature display Adjustment of the displayed temperature value
3 Alarm delay Input of an alarm delay time
4230Vinputs 230 V inputs
5 Sensor type Selection of the temperature sensor of the type L243, K277 or 5K3A1
5.Selectmenu6 Configuration - 2 Controller - 3 Alarm delay.
6Configuration–2Controller–3Alarmdelay.
ALARMVERZ. POS: XXX
Fühlerbruch XXm Alarm delay for sensor fault
Über/Unter Tmp XXXm Alarm delay for high temperature or low temperature
keine Abtauung XXXh Alarm is tripped if no defrost is performed within this configurable time.
Selbsthaltung N NO: Automatic reset of non-transient alarms
YES: Alarms must be reset manually
Exit the menu by tapping the ESCbuttononce.
6.Selectmenu6Configuration–2Controller–6AnalogueInputs.
6 Configuration - 2 Controller - 6 Analogue Inputs
Ain1 aktiv x Use analogue input Z1 (=Y), do not use (=N)
Kältem.Z 1 xxxx Selection of refrigerant zone 1
ND Z1 Min xxx bar Smallestpressurevalueforpressuremonitoringat4mA
ND Z1 Max xxx bar Largest pressure value for pressure monitoring at 20 mA
... ...
AIN2 aktiv x Use analogue input Z2 (=Y), do not use (=N)
Kältem.Z 2 xxxx Selection of refrigerant zone 2
Fkt. AIN2 xxxxx Function of the analogue input Z2:t0Z2 Only for recording t0Z2Reg For
regulation
HD Z2 Min xxx bar Smallestpressurevalueforpressuremonitoringat4mA
HD Z2 Max xxx bar Largest pressure value for pressure monitoring at 20 mA
... ...