5.10.6 Coldroom with defrost heater (controller type UR 141 TE)
The parameters for fan control are::
Thermal fan delay
The fan runs during cooling mode and is stopped during defrosting. When the Fan Delay parameter is set to
”--”ontheUR141TE,thefancontinuesrunningduringdefrosting.
On completion of defrosting, the following conditions apply to starting the fan:
If the thermal fan delay is exceeded on the evaporator sensor after defrosting, the fan will initially not start
soasnottoforceheatintothecoldroom.
After defrosting, the conditions for fan starting are checked only after the drip time has expired.
If on-off control is activated, the following will additionally apply::
The fans are operated with room control.
If the fan is switched off via the coldroom controller, then in order to switch the fan back on via the
coldroomcontrollerthethermalfandelayontheevaporatorsensormustalsobeexceeded.
The fans start when the room controller enables superheat control and stop when superheat control is
disabled.
If a waiting time has been defined, the fans that are running will not be stopped before initiating defrost until
the set waiting time has expired. This allows the refrigerant remaining in the evaporator when the solenoid
valves are closed to evaporate.
The fan remains continuously on when the Fan Delay parameter is set to --.