9.6.4 Menu 3 Clock UK 100 E
CLOCK POS: XXXXX
1 Current Time Move to menu 3-1
2 Defrost Timer Move to menu 3-2
3 Toggle Setpoints Move to menu 3-3
Menu 3-1 Current Time
CLOCK POS: XXXXX Entry Default
Date: XX dd.mm.yy Display and entry of current weekday, date dd.mm.yy
Time: hh.mm Display and entry of current time hh.mm
Daylight Saving X Display and entry of automatic daylight saving
time change (Y/N)
↑,↓,(Y/N) Y
Menu 3-2 Defrost Timer
DEFR.TIMER POS: XXXXX Entry Default
Defrost Timer XXX Defrost initiation via Input D11/12 (EXT) oder internal
(INT)
↑,↓,
(EXT, INT)
EXT
Safe Defr Time XXX m Safe defrost time, i.e. max. allowed duration of
defrosting (internal defrost only); shown only when
paramter defrost timer = INT
0..120 60 min
Manual Defrost XXX Status (ON/OFF) of auxiliary manual defrost *) ↑,↓,
(ON/OFF)
OFF
Def.Tim.Z2 ® Separate defrost timer for zone 2 Menu 3-2-a
Time is defined by time master (system centre / store computer / operator terminal) when CAN bus is
connected. Any entry made will then be overwritten by the defined value.
*)ParameterisNOTautomatically set to ON at first start