EasyManua.ls Logo

ECKELMANN Case Controller UA 4 E Series - Calling the Controller Menu Via Remote Control; System Centre

ECKELMANN Case Controller UA 4 E Series
466 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Firmware V3.13
21.04.2021
183/466
8.3.2 Calling the controller menu via remote control
8.3.2.1 System Centre
The terminal for remote control of the controller (Menu 2-2 or Menu 4-2) is called in the system centre as
follows:
Step 1:Tap"2-Systemoverview"or"4-Configuration"inthemainmenu.If"2"isselected,thevaluesbelow
areonlydisplayedasread-only,for"4",lock-downmustpreviouslyberemovedbyloggingin(Deactivating the
input lock-down)sothatsettingsbelowcanbemade.
Step 2:Tap"2Casecontrollers"andselecttherequiredcontrollerinthelistthatisthendisplayedusingthe
cursorbuttons(↑)and(↓).Inthescreenthatopens,thename,positiondesignationandthealarmpriorityofthe
controller can be input as required.
Step 3: The main menu of the controller is then displayed by tapping the "Remote control" button:
Ifthesystemcentre,storecomputeroroperatorterminalremainslockeddown,settingsonthe
controller are read-only. Changes and inputs are not possible.
However, if any parametrisation is required, the lock-down for the input must be removed, see chapter
Deactivating the input lock-down.
Tip: Detailed descriptions for the basic configuration of the controller and its position designation or
about the settings of important parameters can be found in chapter Basic configuration of the
controller.

Table of Contents

Related product manuals