9.1.4 Menu 3 Clock UA 121 E
CLOCK POS: XXXXX
1 Current Time
Move to menu 3-1
2 Defrost Timer
Move to menu 3-2
3 Toggle Setpoints
Move to menu 3-3
Menu 3-1 Current Time
CLOCK POS: XXXXX Entry Default
Date: XX dd.mm.yy Display and entry of current weekday, date
dd.mm.yy
Time:hh.mm Display and entry of current time
hh.mm
Daylight Saving X Display and entry of automatic daylight saving
time change
(Y/N)
↑,↓,(N/Y)
Y
Menu 3-2 Defrost Timer
DEFR.TIMER POS: XXXXX Entry Default
Defrost Timer XXX Defrost initiation via Input D11/12 (EXT) or
internal (INT)
↑,↓,(EXT,INT)
INT
Safe Defr Time XXX m Safe defrost time, i.e. max. allowed duration of
defrosting (internal defrost only)
0..120
60 min
Manual Defrost XXX Status (ON/OFF) of auxiliary manual defrost *)
↑,↓,(ON/OFF)
OFF
Def.Tim.Z2→ Separate defrost timer for zone 2 Menu 3-2-a
Defr. 1 xxxxx hh:mm Defrost start time for internal defrost; weekday,
time of day;
shown only when paramter defrost timer = INT
↑,↓,
(Mo-Su) or
numbers
(hh:mm)
Mo-Su
01:00
Defr. 2 xxxxx hh:mm Defrost start time for internal defrost; weekday,
time of day;
shown only when paramter defrost timer = INT
↑,↓,
(Mo-Su) or
numbers
(hh:mm)
Mo-Su
07:00
Defr. 3 xxxxx hh:mm Defrost start time for internal defrost; weekday,
time of day;
shown only when paramter defrost timer = INT
↑,↓,
(Mo-Su) or
numbers
(hh:mm)
Mo-Su
13:00
Defr. 4 xxxxx hh:mm Defrost start time for internal defrost; weekday,
time of day;
shown only when paramter defrost timer = INT
↑,↓,
(Mo-Su) or
numbers
(hh:mm)
Mo-Su
19:30
...
Defr. 14 xxxxx hh:mm
Time is defined by time master (system centre / store computer / operator terminal) when CAN bus is
connected. Any entry made will then be overwritten by the defined value.