9.6.7 Menu 6 Configuration UK 100 E
CONFIGURAT POS: XXXXX
1 Refriger. Point Move to menu 6-1
2 Controller Move to menu 6-2
3 Cooling Move to menu 6-3
4 Language Move to menu 6-4
5 Alarm priorities Move to menu 6-5
6 Em.Powersupply Move to menu 6-6
7 COPT+ Move to menu 6-7
Menu 6-1 Refrigeration Point
REFR. PT. POS: XXXXX Entry Default
Refr. Pt. Name: Text only
xxxxxxxxxxxxxxx Free text entry describing refrigeration point (see
note at end of table)
Case Controller
Item ID: XXXXX Free text entry shown after Position (POS:) in
screens (see note at end of table)
UA400
Priority: XX Priority of alarms in failure of refrigeration point or
when setting global controller priority (Menu 6-5)
↑,↓,
or numbers (0..99)
1
Refr. Sys. No.: XX Pack No. of pack controller assigned to case
controller. The controller cannot receive the suction
pressure value for control functions before the
Pack No. of the associated pack controller has
been selected on the case controller
↑,↓,
or numbers (--, 1..9)
--
Refr. Sys. Type XXX Allocation to compressor pack.
Parameter only required for linking to VS 3010 BS
with several zones. Deactivate this parameter (---)
when using pack controllers of other type.
↑,↓,
or numbers (---, Z1, Z2)
Z2
Temp. Zones X Number of temperature zones.
Single-zone operation (tandem mode)
Two-zone operation
↑,↓,
or numbers (1, 2)
2
No. Sensors XX Displays number of temperature sensors
connected.
After pressing ¿, sensor scan is performed and
number of sensors is redefined.