EasyManua.ls Logo

ECKELMANN Case Controller UA 4 E Series - Necessary and Optional Sensors

ECKELMANN Case Controller UA 4 E Series
466 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Firmware V3.13
21.04.2021
33/466
5.5.1 Necessary and optional sensors
Depending on the controller type and the operating mode, there are necessary and optional sensors for the
case controller. A sensor scan is performed automatically during the first start of the controller. The number of
scanned sensors can be checked in the menu (6-1) or with the LDSWin PC software. This allows unconnected
sensorstoberemovedfromthemonitoringforsensorfault.
The following lists show required and optional sensors in the complete design:
Controller type Sensors necessary for regulation Optional sensors - extended functionality
(if terminal available;
see chapter Versions)
Single-zone operation
UA 121 E
UA 131 E / UA 131 E LS
UA 141E
Zone 1: R1.1, R2.1, R4.1, R6.1 Zone 1: R5.1
R1.2, R2.2, R4.2, R5.2, R6.2 (or R4.3, R4.4)
UR 141 NE
UR 141 TE
Zone 1: R1.1, R4.1, R6.1 Zone 1: R2.1, R5.1
R1.2, R2.2, R4.2, R5.2, R6.2
UK 100 E **
KR 160 E **
Zone 1: R4.1, R6.1 Zone 1: R1.1, R5.1
R1.2, R4.2, R5.2, R6.2
Two-zoneoperation-onlyUA400ECC/UA410EAC
UA 121 E
UA 131 E / UA 131 E LS
UA 141E
Zone 1: R1.1, R2.1, R4.1, R6.1
Zone 2: R1.2, R2.2, R4.2, R6.2
Zone1:R5.1(orR4.3)*
Zone2:R5.2(orR4.4)*
UR 141 NEUR 141 TE Zone 1: R1.1, R4.1, R6.1
Zone 2: R1.2, R4.2, R6.2
Zone 1: R2.1, R5.1
Zone 2: R2.2, R5.2
UK 100 E **
KR 160 E **
Zone 1: R4.1, R6.1
Zone 2: R4.2, R6.2
Zone 1: R1.1, R5.1
Zone 2: R1.2, R5.2
*only UA 131 E LS for operation with 4 return air sensors (R4.3 / R4.4 are activated)
** only UA 410 E AC
ATTENTION
Compressor damage! Danger due to liquid refrigerant on the suction side of the compressor!
Operatingmodet
0
via CAN bus (menu 6-2-6)
The evaporator inlet sensors R5.1 and R5.2 should also be connected in the t
0
via CAN
busoperatingmode.Thisresultsinimprovedemergencyrunningcharacteristicsintheeventof
failure of the CAN bus transmission. In standalone operation (without local pressure transmitter),
the sensors, R5.1 and R5.2 must be connected; see chapter Standalone operation using
evaporator inlet sensors!
Operatingmodet
0
local Z1 / Z2 (menu 6-2-6)
In the case of evaporators with high cooling capacity which require high control dynamics, the
superheat control should be realised via a local pressure transmitter (only UA 410 E AC); see
chapters Standalone operation using activated local pressure transmitter and Emergency Op..
Superheat control only via sensors R5.1 and R5.2 is not recommended, as there is a risk of
evaporator flooding due to the slow response behaviour!

Table of Contents

Related product manuals