11 Alarms and messages UA 4xx E
Thetablecontainsallmessagetextsandtheirpossiblecause.Eachmessagetexthasaprioritythatcanbe
set in the Alarm Priorities screen (menu 6-5).
No. Message text Cause Remedy
Hardware error
4 EEPROM error A chip for saving the configuration is
defective or the configuration data in the
EEPROM are not plausible.
Save parameters using the LDSWin
software, possibly initiate first start and
restore parameters using LDSWin. Please
contact Customer Service if the error still
occurs
6 Flash Fault The flash memory module is defective. Please contact Customer Service - replace
device
8 RTC error The real-time clock is defective. Please contact Customer Service - replace
device
10 Battery Voltage The battery for the real-time clock and RAM
backup is discharged.
Replace battery (see chapter Installation
and Startup of UA 4xx E)
Messages
50 First Start The case controller has performed a first
start (loading of the default settings / sensor
scan)
–
51 Power Failure Restart of the controller after a power
failure.
Check230Vpowersupply
120 Low temp. zone 1 Lower limit value at the monitored control
sensors in Zone 1 undercut
Check parametrisation, sensors,
installation
121 Low temp. zone 2 Lower limit value at the monitored control
sensors in Zone 2 undercut
Check parametrisation, sensors,
installation
122 High temp. zone 1 Upper limit value at the monitored control
sensors in Zone 1 exceeded
Check parametrisation, sensors,
installation
123 High temp. zone 2 Upper limit value at the monitored control
sensors in Zone 2 exceeded
Check parametrisation, sensors,
installation
124 Cold room door open
Cold room door Z1/Z2
The cold room door or cold room door Z1 or
Z2 is opened beyond the alarm time; only
for cold room controllers.
Close door, check door switch or
connection cable
125 No Defrost
No defrost within the alarm time.
A consecutive defrost via CAN bus
has not been configured correctly
A master/slave defrost via CAN bus
has not been configured correctly
Check parametrisation: Check the internal/
external defrost timer, defrost times, alarm
delay time, configuration of the master/
slavedefrostviaCANbus(seechapter
Master/slavemode–defrost
synchronisation via CAN bus), check the
configuration of the consecutive defrost via
CAN bus (see chapter Consecutive defrost
(CD) via CAN bus).