9.1.3 Menu 2 Setpoints UA 121 E
SETPOINTS POS: XXXXX
1 Cooling Move to menu 2-1; Special case: When one-zone (tandem) operation is set (Menu
6-1) and setpoint toggle is deactivated (Menu 3-3), Continue to 2-1-1
2 Defrost Move to menu 2-2; Special case: When one-zone (tandem) operation is set (Menu
6-1) and setpoint toggle is deactivated (Menu 3-3), Continue to 2-2-1
3 Not used with this controller type
4 Alarm Move to menu 2-4; Special case: When one-zone (tandem) operation is set (Menu
6-1) and setpoint toggle is deactivated (Menu 3-3), Continue to 2-4-1
5 Rahmenheizung Move to menu 2-5
Menu 2-1 Cooling
COOLING POS: XXXXX
1 Zone 1 Move to menu 2-1-1
2 Zone 2 Move to menu 2-1-2
3 Zone 1T Toggle. Move to menu 2-1-3; not shown when setpoint toggle is deactivated (Menu 3-3)
3 Zone 2T Toggle Move to menu 2-1-4; shown only when two-zone operation is set and when setpoint
toggle is not deactivated (Menu 3-3)
Menu 2-1-1 Zone 1
COOLING 1 POS: XXXXX Entry Default
Setpoint R2.1 XXX °C Supply air temperature setpoint --, -10..20 -2 °C
Hystersis R2.1 X K Supply air temperature hysteresis setpoint; shown only
when on-off control is set (Menu 2-1-1)
1..8 4 K
Setpoint R4.1 XXX °C Return air temperature setpoint --, -10..20 4 °C
Hystersis R4.1 X K Return air temperature hysteresis setpoint; shown only
when on-off control is set (Menu 2-1-1)
1..8 2 K
Superheat XXX K Superheat setpoint Zone 1 0..20 6 K
Min. SH XX K Minimum superheat setpoint, below which cooling
relay
switches off in Zone 1. I-sum (not I-part) is set to zero
when the Reset I-Sum parameter is set to ON.
0..10 2 K
Two pos.ctrl XXX Switch between on-off control (ON) and continuous
control (OFF)
↑,↓(ON/OFF) OFF
MOP-point XXX °C Starting setpoint for MOP mode --, -50..50 –°C
Cool. on AOUT XXX% Kühlung eingeschaltet: fester Wert 0..10 V für
Analogausgang AO1; nur sichtbar, wenn von DIP-
Schalter S3 der Kodierschalter 6 auf ON steht, siehe
Kapitel Funktionsweise der Analogausgänge 0..10 V.
0..100 80 %