Firmware V3.13
21.04.2021
205/466
TOG. SETP. POS: XXXXX Entry Default
emerg.run time XXX % On time in loss of humidity or room air
temperature (via CAN bus); shown only when
mode set to Enthalpy Control (Menu 2-5-3)
--, 0..100 100 %
enthalp. offs. XXX % Offset for on time when enthalpy control is
activated (via CAN bus); shown only when mode
set to Enthalpy Control (Menu 2-5-3)
-50..50 %