Menu 1-3 Defrost Zone 1
DEFROST 1 XXXXX
Defrost XXX Displays current OFF/ON status of defrosting
Temp. R1.1 XXX °C Displays current evaporator defrost termination temperature Input Z31/Z32
Temp. R1.2 XXX °C Displays current evaporator defrost termination temperature Input Z81/Z82; shown
only when single-zone operation is set (Menu 6-1)
Def. End. Tmp. XXX °C Displays defrost termination temperature setpoint for comparison
Wait Time XX m Displays waiting time setpoint
Drip Time XX m Displays drip time setpoint
Last Defrst XX hh:mm Displays time (day, time of day) of last defrost cycle started
M/S Nof. Sl. Number of parameterised and accessible MA slaves
M/S Lost Sl. CAN address of the first MA slave which was not accessible during the last defrost
M/S Defr.Sl. Number of slaves currently undergoing a defrost
M/S DSlMat List of MA slaves currently undergoing a defrost (can be scrolled through using
ENTER)
DSq Nof. Sl. Number of DS slaves (only in the case of DS master)
DSq Lost Sl. CAN address of the first FA slave which was not accessible during the last defrost
DSq Defr.Sl. Number of slaves currently undergoing defrost
DSq DSlMat List of FA slaves currently undergoing a defrost (can be scrolled through using
ENTER)
Menu 1-4 Not used with this controller type.
Menu 1-5 Alarm
ALARM XXXXX
Alarm Relay XXX Displays current OFF/ON status of alarm output Terminal 15/16/18
Hi Temp Setp.1 XX °C Displays high temperature setpoint Zone 1
Lo Temp Setp.1 XX K Displays low temperature setpoint Zone 1
Hi Temp Setp.2 XX °C Displays high temperature setpoint Zone 2; shown only when two-zone operation
is set (Menu 6-1)
Lo Temp Setp.2 XX K Displays low temperature setpoint Zone 2; shown only when two-zone operation is
set (Menu 6-1)