• Menu 1-3 Defrost Zone 1
DEFROST 1 XXXXX
Counting Rate X Displays setpoint for time during which evaporator defrost termination temperature
may be within band around 0°C before defrost counter counts down
Defrost Counter X Displays count for number of defrost cycles to be skipped
Defr. Relay 1 XXX Displays current OFF/ON status of Defrost Relay 1
Temp. R1.1 XXX °C Displays current evaporator defrost termination temperature Input Z31/Z32
Defr. Relay 2 XXX Displays current OFF/ON status of Defrost Relay 2; shown only when single-zone
operation is set (Menu 6-1)
Temp. R1.2 XXX °C Displays current evaporator defrost termination temperature Input Z81/Z82; shown
only when single-zone operation is set (Menu 6-1)
Def. End. Tmp. XXX °C Displays defrost termination temperature setpoint for comparison
Wait Time XX m Displays waiting time setpoint
Drip Time XX m Displays drip time setpoint
Last Defrst XX hh:mm Displays time (day, time of day) of last defrost cycle started
M/S Nof. Sl. Number of parameterised and accessible MA slaves
M/S Lost Sl. CAN address of the first MA slave which was not accessible during the last defrost
M/S Defr.Sl. Number of slaves currently undergoing a defrost
M/S DSlMat List of MA slaves currently undergoing a defrost
(can be scrolled through using ENTER)
DSq Nof. Sl. Number of DS slaves (only in the case of DS master)
DSq Lost Sl. CAN address of the first FA slave which was not accessible during the last defrost
DSq Defr.Sl. Number of slaves currently undergoing defrost
DSq DSlMat List of FA slaves currently undergoing a defrost
(can be scrolled through using ENTER)