EasyManua.ls Logo

ECKELMANN Case Controller UA 4 E Series - Page 249

ECKELMANN Case Controller UA 4 E Series
466 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Firmware V3.13
21.04.2021
249/466
DEFR.TIMER POS: XXXXX Entry Default
Defrost Timer XXX Defrost initiation via Input D11/12 (EXT) or
internal (INT)
↑,↓,(EXT,INT)
INT
Safe Defr Time XXX m Safe defrost time, i.e. max. allowed duration of
defrosting (internal defrost only)
0..120
60 min
Manual Defrost XXX Status (ON/OFF) of auxiliary manual defrost *)
↑,↓,(ON/OFF)
OFF
Def.Tim.Z2→ Separate defrost timer for zone 2 Menu 3-2-a
Defr. 1 xxxxx hh:mm Defrost start time for internal defrost; weekday,
time of day;
shown only when paramter defrost timer = INT
↑,↓,
(Mo-Su) or
numbers
(hh:mm)
Mo-Su
20:15
...
Defr. 14 xxxxx hh:mm
*) Parameter is automatically set to ON at first start for the duration of the safe defrost time.

Table of Contents

Related product manuals