DEFR.TIMER POS: XXXXX Entry Default
Defrost Timer XXX Defrost initiation via Input D11/12 (EXT) or
internal (INT)
↑,↓,(EXT,INT)
INT
Safe Defr Time XXX m Safe defrost time, i.e. max. allowed duration of
defrosting (internal defrost only)
0..120
60 min
Manual Defrost XXX Status (ON/OFF) of auxiliary manual defrost *)
↑,↓,(ON/OFF)
OFF
Def.Tim.Z2→ Separate defrost timer for zone 2 Menu 3-2-a
Defr. 1 xxxxx hh:mm Defrost start time for internal defrost; weekday,
time of day;
shown only when paramter defrost timer = INT
↑,↓,
(Mo-Su) or
numbers
(hh:mm)
Mo-Su
20:15
...
Defr. 14 xxxxx hh:mm
*) Parameter is automatically set to ON at first start for the duration of the safe defrost time.