Menu1-4Notusedwiththiscontrollertype.
Menü 1-5 Alarm
ALARM XXXXX
Alarm Relay XXX Displays current OFF/ON status of alarm output Terminal 15/16/18
Hi Temp Setp.1 XX °C Displays high temperature setpoint Zone 1
Lo Temp Setp.1 XX K Displays low temperature setpoint Zone 1
Hi Temp Setp.2 XX °C Displays high temperature setpoint Zone 2; shown only when two-zone operation
is set (Menu 6-1)
Lo Temp Setp.2 XX K Displays low temperature setpoint Zone 2; shown only when two-zone operation is
set (Menu 6-1)
Menu 1-6 Frame Heater
MODE XXXXX
Frame Heater XXX Displays current OFF/ON status of frame heater output Terminal 91/92/93
Run Time XXX % Displays current frame heater on time
Humidity XXX % Displays current room air humidity (transmitted via CAN bus from VS pack controller
with fitted humidity sensor)
Room temp. XX °C Displays current room air temperature (tranmitted via CAN bus from VS pack controller
with fitted room air temperature sensor)
Menu 1-7 Cooling Zone 2
COOLING 2 XXXXX
COOLING XXX Displays current OFF/ON status of cooling
op.deg. Z 2 XX % Displays current valve opening degree Zone 2
OD med. 24h XX % Displays mean valve opening degree Zone 2 for past day
Temp. R2.2 XXX °C Displays current supply air temperature Input Z61/Z62
Setpoint R2.2 XXX °C Displays supply air temperature setpoint for comparison
Hystersis R2.2 XXX K Displays supply air temperature hysteresis setpoint; shown only when on-off control is set (Menu 2-1-2)
Temp. R4.2 XXX °C Displays current return air temperature Input Z71/Z72
Setpoint R4.2 XXX °C Displays return air temperature setpoint for comparison
Hystersis R4.2 XXX K Displays return air temperature hysteresis setpoint; shown only when on-off control is set (Menu 2-1-2)
SH Z 2 XXX °C Displays current superheat temperature Zone 2
sup air ctrl XXX Displays current OFF/ON status of supply or return air control
MOP op. XXX Displays OFF/ON setpoint of MOP mode
Status hand XXX Status manual shutdown (ON/OFF)